BESS Power Station: Centralized Fire Protection Solution
Description
In order to meet the growing fire protection needs of energy storage stations, Guo Anda launched the "1+ N Intensive Fire Protection Solution" and innovatively developed a centralized fire suppression system, which can simultaneously perform all-round "Pack- and Container-Level" fire protection for multiple BESS units; Integrating multiple leading technologies such as multi-unit real-time monitoring, intelligent centralized management, and precise pack-level gas-liquid fire suppression, it can realize all-weather fire monitoring of multiple BESS units, and perform accurate fire extinguishing when a fire occurs. Equipped with a large-capacity extinguishant, it can carry out multiple long-term suppression of fires in the BESS units; Comprehensively using the emerging information technologies such as IoT, cloud computing, and big data, it can realize the intelligent visual management, present real-time fire protection dynamics in the most intuitive way, which greatly improves the fire protection risk management and comprehensively guarantees the safe and reliable operation of the equipment in electrochemical energy storage power station.
System Features
1.Centralized intelligent management
The solution adopts the centralized fire suppression system, with the compressed air foam extinguishing device as the center. The pipeline length is up to 100m, and can be connected to up to 200 containers. This system can conduct automatic and accurate all-weather fire extinguishing and conduct the operation status monitoring of the fire extinguishing system in the BESS, and upload the information in real time to the fire alarm controller, which can be quickly viewed and managed on the display device at the fire alarm controller.
2.Large-capacity extinguishant
This system adopts built-in 600L extinguishant storage tank. When the energy storage container is used as the protected unit, the extinguishant can be continuously sprayed for at least 120min; if the intermittent spraying for continuous suppression and cooling are used, more than 100 spraying can be carried out.
3.Industrial control environment adaptation
The system is equipped with industrial-grade multi-functional air conditioners, dehumidifiers, exhaust fans and electric heating devices, which can realize the intelligent control of humidity and temperature in the cabin, and provide a strong guarantee for the stable equipment operation under various environmental conditions.
4.Long-distance and high-efficiency suppression
The system is equipped with strong power, and the longest distribution distance can reach up to 100m, and it still maintains strong extinguishing power at the farthest end, so that the system can provide flexible layout solutions according to the working conditions and environments of the project site.
5.Backup support
In order to further ensure the effectiveness, the system adopts the design of one use and one standby for the key power module, with standby power available, which can effectively prevent the failure of the fire extinguishing system caused by the sudden failure of its power source when the alarm occurs, and can effectively guarantee the operation stability of the fire extinguishing system.
6.Intrinsically safe prevention and control
In order to comprehensively prevent and control the fire risks in the energy storage power station, the equipment cabin itself has a full set of fire alarm system and automatic fire extinguishing system, which can monitor the status of the equipment itself in real time. When there is an emergency, it can be activated in time and quickly send out an alarm signal for automatic fire extinguishing, which can effectively ensure the safe operation of the equipment.
Fire Suppression System
Item | Specification & Parameter |
---|---|
Operating voltage | AC380V 50HZ |
Maximum power | 20KW |
Operating temperature | -40°C~+55°C |
Working humidity | 0 ~ 95% RH |
Protection class | IP55; Enclosure’s anti-corrosion rating: C4 |
Rated working pressure | 0.8 MPa |
Rated flow rate | 4m3/h |
Storage capacity of extinguishant | 400L |
Filled extinguishant | FK-5-1-12 |
Maximum filling mass | 600kg |
Maximum number of extensions | 16 units |
Sprayed BESS number at the same time | 2 |
Spraying number | 3~ 20 times (adjustable per the actual filling mass) |
Dimension | 4500°24'31"2500 |
Weight | 7.5 T |
Standby voltage | AC400V |
Standby electric quantity | 5KW * H |
Standby power | 17KW |
Communication | CAN/485/Passive dry contact |